A 12-Foot Raised Floor?

Posted By Rich Miller On June 3, 2009 @ 9:40 am In Europe,Hewlett-Packard | 6 Comments

That’s not a typo. A new data center being built by EDS in England will use an unusual architecture for its free cooling system, treating the entire 12-foot high first floor of the facility as a cold air plenum, with the server cabinets housed on the second floor. The 305,000 square foot facility in Wynyard is being called “Eco 2″ for its energy efficiency features.

The fresh air will be introduced into the plenum by 7-foot high low-velocity fans designed to maintain a consistent air pressure across the entire room/plenum. Slotted vents in the ceiling allow the fresh air to enter the cold aisles of the data center, which are fully-enclosed by a cold-aisle containment system. The containment allows the system to operate with lower airflow rate than typical raised floors in an open hot aisle/cold aisle configuration.

By preventing the mixing of cold and warm air, the containment system will also allow EDS to maintain a higher temperature in the cold aisle, which allows additional energy savings. In an animated virtual tour [1] on the EDS web site (link via Patrick Thibodeau at ComputerWorld [2]), the company says it can maintain the cold aisle at 86 degrees, rather than 68 degrees.

HP/EDS officials say they believe this design is a “relatively new approach.” The first phase of the project will feature four data halls (“pods”) each offering 10,900 square
feet of space. EDS says the facility will support 210 watts per square foot across the floor.

About Rich Miller [3]

Rich Miller is the founder and editor-in-chief of Data Center Knowledge, and has been reporting on the data center sector since 2000. He has tracked the growing impact of high-density computing on the power and cooling of data centers, and the resulting push for improved energy efficiency in these facilities.


Article printed from Data Center Knowledge: http://www.datacenterknowledge.com

URL to article: http://www.datacenterknowledge.com/archives/2009/06/03/a-12-foot-raised-floor/

URLs in this post:

[1] virtual tour: http://www.eds.com/news/features/5138/

[2] ComputerWorld: http://www.networkworld.com/news/2009/060209-hp-uses-outside-air-big.html

[3] Rich Miller: http://www.datacenterknowledge.com/archives/author/richm/

Copyright © 2011 Data Center Knowledge. All rights reserved.